NYAF Wilson

NYAF Cable (Cu/PVC-f) – Wilson Cable

Type: NYAF (Cu/PVC-f)

Code Name: 60227 IEC 02

Rated Voltage: 450/750 V

Size: 1.5 ~ 120 mm²

Standard: SNI 04-6629.3 – 2006

Application: Permanent installation in conduit or exposed wiring in dry location.

Construction & Electrical Data

Nominal Cross Section Area (mm²)Overall Diameter (mm)Cable Weight (kg/km)ConductorInsulationCurrent Carrying Capacity at 30°C (A)Short Circuit Current 1 sec (kA)
Nominal Cross Section Area (mm²)DC Resistance at 20°C (Ω/km)Min. (MΩ/km)Max. (MΩ/km)In PipeIn Air
1.53.022.481.513.30.0100.01515240.17
2.53.6535.152.57.980.0090.0220320.29
44.252.0044.950.0070.02525420.46
64.872.2463.30.0060.03433540.69
106.3120.83101.910.00560.04545731.16
167.4183.18161.210.00460.06161981.84
259.3287.32250.7800.00440.078831382.88
3510.7389.47350.5540.00420.0951031734.03
5012.7560.78500.3860.00370.1321371975.75
7014.6770.30700.2720.00320.1561652458.05
9516.81030.82950.2060.00320.19719729510.93
12018.51290.501200.1610.00310.24523534513.8